CASE 02 Retail / secondary pump network

Raffles City Ningbo

157,000 m² · secondary pump network · retail plant
Location
Ningbo, Zhejiang · Daqing South Road
Floor area
157,000 m² (opened 2012)
Cooling
5×800 RT + 1×250 RT centrifugal chillers
Terminals
All-air + fan coils + fresh air
Scope
BAS integration / VFDs / AI optimisation
3.0 → 4.4Plant EER (cumulative)Cumulative EER
−23.1%Weekday similar-day plant energyWeekday test
20.3%Summer savingSummer saving

Context and challenge

Retail load swings with footfall and trading hours, so the plant starts and stops constantly. The existing Johnson Controls BAS was hard to operate and unstable; eight cooling towers ran on fixed staging while the cooling and secondary pumps stayed at fixed frequencies.

Savings could not come at the cost of comfort, and the works had to be completed at night and between trading hours.

What we did

  • Platform integration: both BAS consolidated so chillers, pumps and towers are coordinated from one view.
  • VFD retrofit: variable speed drives added to the primary chilled-water pumps (cooling and secondary pumps already had VFDs).
  • Strategy upgrade: pump frequency optimisation from pipe characteristics, dynamic chilled-water temperature from outdoor temperature, cooling-tower approach control from wet-bulb temperature, plus self-learning tower staging.
  • Similar-day verification: separate weekday and weekend comparisons of total plant energy with measures off and on.

Result

Cumulative plant EER improved from 3.0 to 4.4. The cooling season saved about 290 MWh, cutting roughly 278 tonnes of CO₂, with a 20.3% summer saving rate and automation raised to 99%. The two similar-day pairs delivered 23.1% (weekday) and 17.9% (weekend).

Project note

Tower and pump sequencing is the most overlooked saving in retail plants. Once the system learns the best-efficiency point it stages equipment itself — consistently, and without depending on who is on shift.

02 Data / TEST RECORD

Two similar-day pairs, summer

ConditionTest datePeak outdoorPlant energySaving
Measures off (weekday)2024-07-0838 °C19,753 kWh—
Measures on (weekday)2024-08-0138 °C15,202 kWh23.1%
Measures off (weekend)2024-07-0737 °C15,835 kWh—
Measures on (weekend)2024-08-1137 °C13,150 kWh17.9%
Summer average———20.3%

Tested to GB/T 31349-2014; the average of the two similar-day pairs is reported as the season's saving rate.

Comparable systems,
different results

We keep the full test record and strategy log for this project. If your plant looks similar, start with a measured audit before committing to a retrofit.